What is the fault of the generator fault light and common faults and solutions

发表时间:2019-12-25 Article source : Couch motor manufacturersPublished time: 2019-12-25

In the process of the generator, if the fault light is on, we need to stop the work in time to check the cause of the light. Generally, the reasons for the light are the poor combustion status of the generator, the generator knocking, or the internal cause of the generator. For example, the quality of the fuel is not good, the generator cylinder is not rushed, etc., will cause the fault light to light up, the following details for everyone!


First, what is the problem when the generator fault light is on?

1. Poor combustion status: The bad combustion status of the engine is the main reason for the engine fault light to illuminate.

2. There are usually three cases of engine knock: the car is weak; the car is weak, the engine noise is too loud; there is obviously a knock on the cylinder.

In the first case, some engine fault lights will be on, and some will not be on. In the second and third cases, the engine fault lights will be on.

3. The internal cause of the engine fault light is on: the fuel quality is not good; the inside of the engine cylinder is not clean and there is deposited carbon.


Common faults and solutions of generators

1. The generator does not operate according to the specified technical conditions, such as the stator voltage is too high, the iron loss increases; the load current is too large, the stator winding copper loss increases;

If the frequency is too low, the cooling fan speed will be slowed down, which will affect the heat dissipation of the generator. If the power factor is too low, the rotor excitation current will increase and the rotor will heat up. Check that the indication of the monitoring instrument is normal. If it is abnormal, necessary adjustments and treatments shall be carried out to make the generator run according to the specified technical conditions.

2. The three-phase load current of the generator is unbalanced, and the overloaded one-phase winding will overheat; if the difference between the three-phase currents exceeds 10% of the rated current, it is a serious phase current imbalance, and the three-phase current imbalance will produce a negative Sequential magnetic field, thereby increasing losses, causing magnetic pole windings and ferrules and other components to heat up. The three-phase load should be adjusted to keep the current of each phase as balanced as possible.

3. The air duct is blocked by dust accumulation and poor ventilation, which makes it difficult for the generator to dissipate heat. The dust and grease on the air duct should be removed to make the air duct unobstructed.

4. The inlet air temperature is too high or the inlet water temperature is too high, and the cooler is blocked. Reduce the inlet air or water temperature to clear the blockage in the cooler. Before the fault is eliminated, the generator load should be limited to reduce the generator temperature.

5. Too much or too little grease should be added to the bearing according to the regulations, usually 1/2 to 1/3 of the bearing chamber (the lower limit for the low speed and the lower limit for the high speed), and the bearing should not exceed 70% of the room is suitable.

6. Bearing wear. If the wear is not serious, the bearing will overheat locally; if the wear is serious, the stator and rotor may be rubbed, causing the stator and rotor avoiding parts to overheat. The bearings should be checked for noise. If friction between the stator and rotor is found, stop the machine immediately for maintenance or replace the bearings.

7. The stator core insulation is damaged, which causes a short circuit between the chips, which causes the local eddy current loss of the core to increase and heat, and in serious cases, the stator windings will be damaged. Stop immediately for maintenance.

8. The parallel wires of the stator winding are broken, causing the current of other wires to increase and generate heat. Stop immediately for maintenance.

The above is the introduction of "What is the problem of the generator fault light is on, and common faults and solutions", I hope to help you!

下一篇:没有了 Next: Nothing Next: No

everybody is watching

  • 小负荷柴油发电机组在工作时有哪些故障
    In the power generation industry in China, we have been working hard, pursuing the concept of quality and service, and for the sake of customers, the full power generator chooses China and your generator is a professional housekeeper. At present, the diesel generator set maintenance market refers to damage inspection and routine maintenance. Two aspects: after maintenance refers to the failure of the diesel generator, there are problems with various accessories, such as replacing the generator or
  • 同步发电机一般常见问题的处理
    The diesel engine is working normally, but the generator fails to generate electricity or the voltage is very low. This may be due to the components associated with the generator, such as: the exciter is damaged, and the excitation voltage cannot be supplied. The excitation current is taken in. The rotor's dead center residual magnetism is weakened or declining. It will make the generator unable to generate electricity or the transmission voltage is extremely low. The right to respond is usually: use an appropriate DC voltage and directly connect to the excitation winding according to the polarity Magnetization. Carefully inspect the exciter and the cyclotron rectifier, find abnormal components or windings, and replace them for restoration. The generator's transmission voltage is unstable, and
  • 发电机租赁必须对它的操纵规程有一定的认识
    Before starting, you should check whether the fuel volume of the fuel tank is rich, and there is no oil leakage in each oil pipe and the discussion area; whether the cooling system water is rich, clean and leak-free, and whether the fan belt is tight or not. The internal combustion engine and generator drive parts should be connected and trusted. The wires of the input line are well-insulated, complete and effective in all aspects. After starting, it should run at low speed for 3 to 5 minutes. After the temperature and oil pressure wheel are normal, the initial work can be done. The generator should be no different in the speed increase. Ring, the slip ring and commutator are well brushed, no jumping and sparking phenomenon. After the operation is stable and the frequency and voltage reach the rated value, power can be supplied to the outside.
  • 介绍柴油发电机组辨别冒烟颜色启动从预热开始
    Blue smoke, fire reason: It means that the engine is burning oil. There are three types of reasons: first, the piston ring goes opposite, and the oil comes in the cylinder; the second is the oil level of the oil pan of the atmosphere filter, which leads the ring. The height of the groove; Third, the gap between the duct and the valve stem is too poor. Expulsion idea: Adjust the piston ring so that the opening teeth of the ring are staggered 120 degrees or 180 degrees, and the opening teeth of the ring should avoid the piston pin hole and the side pressure is poor. Adjust the height of the oil level of the oil filter of the atmosphere filter below the height of the annular groove; if the clearance between the duct and the valve stem is too poor, replace the component and reduce the clearance. The normal mutual assistance clearance between the two is 0.0